Low Voltage Current Transformer 400/5

Low Voltage Current Transformers

The CT current transformers deliver at the secondary a current (0-5 A) proportional to the current measured at the primary. This means that they can be used in combination with measurement devices (switchboard instrumentation, kilowatt-hour meters, power-monitoring units, etc.)

Advantages

  • A broad selection of ratings : from 40 to 6000A
  • Safety : sealable insulating cover
  • Installation : on symmetrical DIN rail, on mounting plate, on busbar

Low Voltage Current Transformer

current transformer in kenya

The Ip/5 A ratio low voltage current transformer delivers at the secondary a current (Is) of 0 to 5 A that is proportional to the current measured at the primary (Ip). This allows them to be used in combination with measurement equipment:

  • Ammeters.
  • Kilowatt-hour meters.
  • Measurement units.
  • Control relays etc.

When the primary is energized, the measurement equipment nearly acts as a short circuit which keeps the secondary voltage very low. This voltage will increases significantly if the short circuit is removed.

Low Voltage Current Transformer selection – conductor rating aspects

 

The choice depends on the conductor profile and the maximum intensity of the primary circuit.

  • We recommend that you choose the ratio immediately higher than the maximum measured current (In). Example: In = 1103 A; ratio chosen = 1250/5.
  • For small ratings: From 40/5 to 75/5 and for an application with digital devices, we recommend that you choose a higher rating, for example 100/5.
  • This is because small ratings are less accurate and the 40 A measurement, for example, will be more accurate with a 100/5 CT than with a 40/5 CT.
  • Specific case of the motor starter: to measure motor starter current, you must choose a CT with primary current Ip = Id/2 (Id = motor starting current).